The TMV fail-safe test explained

The fail-safe test, sometimes called the cold isolation test, checks that a thermostatic mixing valve shuts down when its cold supply is lost. This guide goes through the test step by step, explains what a pass looks like, sets out the usual reasons a valve fails, and describes what should happen next.

A thermostatic mixing valve with a temperature test gauge fitted to its outlet

Why the test matters

In normal use a TMV blends hot and cold water to a set temperature. The danger comes when the cold supply suddenly drops away, perhaps because of a burst pipe, a tank running dry, maintenance elsewhere in the building or a blocked strainer. Without cold water to mix with, an ordinary mixer would send full-temperature hot water straight to the outlet.

A TMV is built to respond to that by closing its hot port, so the flow stops or falls to a trickle. The fail-safe test recreates the loss of cold supply in a controlled way to prove the valve still does this. It is carried out at commissioning and at every in-service test, and it is often the first thing to show that a valve needs servicing.

The test, step by step

Procedures vary slightly between manufacturers and sites, but the D 08 in-service test follows this broad sequence.

  • 1. Check the supplies

    The hot and cold supply temperatures at the valve are measured and recorded, so the conditions of the test are known.

  • 2. Run the outlet and record the mixed temperature

    The outlet is run at its normal flow until the temperature settles, and the mixed temperature is measured in the stream with a calibrated thermometer and recorded.

  • 3. Isolate the cold supply

    The cold supply to the TMV is shut off at its isolating valve while the outlet stays open.

  • 4. Observe the flow

    Within a few seconds the flow from the outlet should stop or reduce to a trickle. Any water that does still flow is checked, and the observation is recorded.

  • 5. Restore the cold supply

    The cold isolating valve is opened again and the outlet is left running for the temperature to settle.

  • 6. Re-measure

    The mixed temperature is measured again and compared with the reading from step 2.

  • 7. Record the result

    The result, the readings and any action taken are written up against the valve.

What a pass looks like

  • Flow stops or becomes a trickle

    When the cold is isolated, the outlet should not keep running hot. A full stop or a small, clearly reduced trickle is the expected response.

  • Temperature recovers

    Once the cold is restored, the mixed temperature should return close to its earlier reading, commonly within about 2°C.

  • The setting is still right

    The recovered temperature should also still be within the acceptable range for that outlet, for example no more than 41°C at a washbasin under D 08.

  • Supply hot water stays hot

    A pass is only meaningful if the hot supply was at its normal temperature during the test, which is why supply readings are recorded first.

Why valves fail the test

  • Scale

    Limescale on the shuttle, element or seats slows or stops the movement that closes the hot port. This is the most common cause in hard water areas.

  • A worn or tired cartridge

    Thermostatic elements lose responsiveness over time, and seals and springs wear. The valve may still mix water normally but react too slowly when the cold fails.

  • Failed check valves

    If a check valve lets water pass the wrong way, hot water can cross into the cold side when the cold is isolated, so the outlet keeps running warm or hot.

  • Blocked strainers

    A part-blocked strainer starves one side of the valve, which upsets both the normal mixed temperature and the test result.

  • Unsuitable or unbalanced supplies

    A valve fitted on a pressure it is not approved for, or with very different hot and cold pressures, may not behave as designed.

  • Debris

    Grit or sediment from mains work or old pipework can lodge in the cartridge and stop it closing fully.

What happens after a failure

A valve that fails the fail-safe test is not giving the protection it was fitted to provide, so the outlet should be made safe straight away in line with the site's procedures. That may mean taking the outlet out of use, restricting access to it or making sure only supervised use takes place until it is fixed.

The usual next step is to service the valve: clean the strainers, descale or replace the cartridge, check or renew the check valves, and then recommission the valve and test it again. If the valve still fails, or parts are no longer available, replacement is normally the answer. Because the valve has effectively been recommissioned, the early in-service test pattern starts again, and the failure, the work done and the new readings are all recorded. Our guide to TMV testing intervals explains how this feeds into the routine.

Fail-safe test questions

See all questions

Is it safe to carry out a fail-safe test?

It is designed to be done under controlled conditions with the outlet running and nobody using it. Hot water may briefly run at the outlet if the valve fails, so care is needed.

Should the hot supply be isolated as well?

Some procedures also check the valve's response to loss of hot supply, particularly for valves approved for healthcare use. The site's procedure and the manufacturer's instructions say whether this is needed.

What if there is no isolating valve on the cold supply?

The test cannot be done properly without one. Fitting isolating valves is usually recommended so the TMV can be tested and serviced.

How long does the flow take to stop?

It should happen within a few seconds of the cold being isolated. A slow or partial response is a sign the valve needs attention.

Can a valve pass the temperature check but fail the fail-safe?

Yes. A valve can still blend water to the right temperature while its response to supply failure has become sluggish, which is why both checks are made.

Should a failed valve be left in use until it is fixed?

Generally no. The outlet should be managed in line with the risk assessment until the valve has been repaired and passes the test.